ADC - AC/DC Supply & Battery Charger
AC/DC SUPPLY CHARGER
Look at picture.
This assembly is a combination power supply and battery charger
that inputs 120-240VAC mains power, and supplies an uninterrupted
source of 12VDC power for critical devices.
Aside from supplying an uninterruptible 12VDC power source, the
assembly features a "low battery alarm" indication signal
(for local and/or remote monitoring) and a load shed function
that protects the attached standby battery from deep discharge.
__________________________________________
APPLICATIONS
- Powering control and communication equipment
- PLC, IOC, RTU, SLC uninterruptible power
- Field instrument power
__________________________________________
FEATURES
- Combination charger and supply circuits
- Load shed circuit to protect batttery from deep discharge,
and lengthen it's useful life
- Compact size for installation efficiencies
- Rapid recharging capability for minimal downtime
- Industrial quality components and workmanship for long and
reliable operation
__________________________________________
SPECIFICATIONS
__________________________________________
Operating environment (electronics)
- Standard -10 to +70°C temperature
- 0 to 95% relative humidity (non-condensing)
__________________________________________
Input power
- Input power: 120VAC ±10%, 50-60Hz, via supplied external
transformer and fuse. Board assembly inputs 28VAC from transformer
secondary winding
__________________________________________
Output power
- Main output: 13.6VDC ±3%, 2A (battery backed-up)
- Maximum combined output current is 1.5A, leaving a 0.5A reserve
for battery charging current
__________________________________________
Transient protection
- Meets or exceeds IEEE C37.90A-1987
surge withstanding specification
__________________________________________
Auxiliary operations
- Low battery alarm: 11.5V ±3%
- Low battery alarm signal: Open collector to Power Common (sinks
10mA from 28VDC source)
- Low voltage cutout (battery load shed) occurs at 10V
±3%
- Restoral from low voltage cutout occurs when battery voltage
reaches 12.5V ±3%
__________________________________________
ADDITIONAL INFORMATION
Push the "BACK" button in your browser program after
viewing the following pages, to return to this page:
Look at picture.
__________________________________________
ORDERING INFORMATION
200062: AC/DC SUPPLY/CHARGER ASSEMBLY
200062-000 $211
See standby batteries.
Go back to CATALOG top page
Go back to ADC home page